ATG alarms explained: what they mean and what to check first

An automatic tank gauge (ATG) console names its alarms in a few words, like “Sudden Loss Alarm” or “PLLD Shutdown Alarm”. Here’s what the common ones mean and where to look first. The names are the ones Veeder-Root TLS consoles use; Franklin Fueling EVO, OPW ProGauge and other consoles use similar names for the same conditions.

This is a starting point, not a repair manual. Follow the console’s documentation and your site’s procedures, and call your service company when an alarm points to a leak or keeps coming back.

Jump to

Tank level and inventory

From the probe in each tank: how much fuel there is and whether it changed when it shouldn’t have. See also: How to stick a fuel tank.

Overfill Alarm

What it means: The fuel level passed the overfill limit — the tank could overflow.

What to check first: Stop the delivery and check the fill and spill area.

Maximum Product Alarm (also: Max Product Alarm)

What it means: The fuel level is at the tank's maximum safe volume.

What to check first: Stop any delivery immediately and confirm the level with a stick reading.

High Product Alarm

What it means: The fuel level is above the high limit: the tank is nearly full.

What to check first: Make sure no delivery is still going in, and hold further deliveries until fuel is sold down.

Low Product Alarm

What it means: The fuel level is below the low limit.

What to check first: Order a delivery. If the reading looks wrong, stick the tank.

Delivery Needed Warning

What it means: Fuel has dropped below the reorder level.

What to check first: Schedule a delivery.

Invalid Fuel Level Alarm

What it means: There's so little fuel that the probe's fuel and water floats are too close together to read.

What to check first: Deliver fuel; the reading recovers once the level rises.

Sudden Loss Alarm

What it means: Fuel dropped while the tank should have been idle.

What to check first: Look for a large leak or theft, and compare against dispenser activity at that time.

HRM Reconciliation Warning (also: Reconciliation Alarm)

What it means: Book inventory and measured inventory disagree by more than the limit.

What to check first: Look for a leak, theft or meter error.

Missing Delivery Ticket Warning

What it means: A delivery was detected but its ticket wasn't entered.

What to check first: Enter the delivery ticket at the console.

Water, temperature and fuel quality

The probe’s water float and temperature sensors, and density on consoles that measure it. See also: Water in your fuel tank.

High Water Warning

What it means: Water in the bottom of the tank is approaching the high-water limit.

What to check first: Plan to have the water removed, and find where it is getting in.

High Water Alarm

What it means: There is too much water (or phase-separated fuel) in the bottom of the tank.

What to check first: Have it pumped out, and check fill caps, risers and the tank for where water gets in.

Cold Temperature Warning (also: Low Temp Warning)

What it means: The probe is too cold (below about -4°F) to read accurately, so readings are paused.

What to check first: Nothing to do; it clears once the probe warms above about 0°F.

Fuel Quality Alarm

What it means: Possible water contamination, phase separation or the wrong product in the tank.

What to check first: Take a sample from the tank bottom.

Density Warning

What it means: The measured fuel density is outside the tank's set limits — possibly the wrong or contaminated product.

What to check first: Check what was last delivered and verify the density limits.

Probes

When the console can’t get a good reading from a tank’s probe.

Probe Out Alarm

What it means: The console can't read the tank probe.

What to check first: Check the probe's wiring and connections, then the probe itself.

Probe Malfunction (also: Unstable Probe)

What it means: The tank probe's readings are bad or erratic.

What to check first: Check wiring and splices; the probe may need replacing.

Tank leak tests

In-tank leak tests the console runs while the tank is quiet, and continuous statistical tests (CSLD).

Gross Leak Test Fail Alarm

What it means: The tank failed its 3 gph leak test.

What to check first: Re-run the test; call for service if it fails again.

Periodic Leak Test Fail Alarm

What it means: The tank failed its 0.2 gph (monthly) leak test.

What to check first: Re-run the test when the tank is quiet; call for service if it fails again.

Annual Leak Test Fail Alarm

What it means: The tank failed its 0.1 gph (annual) leak test.

What to check first: Re-run the test, then call for service.

Periodic Test Needed Warning (also: Periodic Test Needed Alarm)

What it means: The tank's required leak test hasn't passed recently enough.

What to check first: Schedule or run the test.

Leak Test Active

What it means: A tank leak test is running.

What to check first: Avoid dispensing from this tank until the test finishes.

No CSLD Idle Time Warning

What it means: The tank had too little quiet time in 24 hours to run its continuous leak test.

What to check first: Allow idle periods, and check the pump-sense wiring.

CSLD Rate Increase Warning

What it means: The continuous leak test saw the volume rise when it should not — something may be getting into the tank.

What to check first: Check for water getting in or a stuck pump relay.

Siphon Break Active Warning

What it means: The siphon valve has isolated this tank from its manifold for a test.

What to check first: Nothing to do; it clears when the test ends.

AccuChart Calibration Warning

What it means: Automatic tank-chart calibration doesn't have good enough data yet.

What to check first: Check the tank dimensions and meter setup; it usually resolves with normal sales and deliveries.

Pressurized line leak detection (PLLD)

The electronic line leak detectors on pressurized product lines: their tests and the pressure they see.

Gross Test Fail Alarm

What it means: The line failed its 3 gph leak test, so dispensing on it may be stopped.

What to check first: Inspect the sumps and piping for leaks, check the line's diagnostics, then re-test.

Periodic Test Fail Alarm

What it means: The line failed its 0.2 gph (monthly) leak test.

What to check first: Inspect the sumps and piping and re-test. Air in the line can also cause this.

Annual Test Fail Alarm

What it means: The line failed its 0.1 gph (annual) leak test.

What to check first: Inspect the sumps and piping and re-test.

Periodic Test Needed Warning (also: Gross Test Needed Alarm)

What it means: The line's required leak test hasn't passed recently enough.

What to check first: Allow quiet time with no dispensing so the test can run, or start one manually.

Shutdown Alarm (also: PLLD Shutdown Alarm)

What it means: The line has been shut down because of a failed test or another alarm assigned to it.

What to check first: Find and fix the alarm that triggered it; the line comes back once that clears.

Sensor Open Alarm (also: PLLD Open Alarm)

What it means: The line's pressure sensor reads as disconnected or impossibly low.

What to check first: Check the pressure transducer and its wiring; a passing 3 gph test clears it.

Sensor Short Alarm

What it means: The line's pressure sensor wiring is shorted.

What to check first: Check the transducer wiring.

High Pressure Alarm (also: High Pressure Warning)

What it means: Line pressure is staying too high.

What to check first: Look for a blockage or an extra check valve in the line.

Low Pressure Alarm

What it means: The line didn't build normal pressure when the pump ran.

What to check first: Check the pump, its power and relay, and the line's check valve.

Continuous Handle On Alarm (also: Continuous Handle On Warning)

What it means: A dispenser handle signal has been on far too long.

What to check first: Check for a stuck nozzle, handle switch or call signal.

Fuel Out Alarm

What it means: The tank is too low for the line to pump (about 10 inches or less), so the pump is locked out.

What to check first: Order fuel.

Line Equipment Alarm

What it means: The line leak detector's equipment has a fault.

What to check first: Check the pressure transducer, its controller and wiring; call for service if it persists.

Sensors

Liquid, vapor, groundwater and interstitial sensors in sumps, dispenser pans, tank walls and monitoring wells.

Fuel Alarm

What it means: Fuel was detected where the sensor is (sump, pan, interstitial space or well).

What to check first: Inspect that area for a leak right away.

Water Alarm

What it means: Water was detected at the sensor.

What to check first: Inspect the sump or pan, find where the water is getting in and pump it out.

High Liquid Alarm

What it means: Liquid is high in the sump, pan or wall space.

What to check first: Inspect the area, find where the liquid is coming from and remove it.

Low Liquid Alarm

What it means: The liquid level in the tank wall space dropped — a wall may be leaking.

What to check first: Call for service.

Liquid Warning

What it means: A small amount of liquid has reached the sensor.

What to check first: Inspect the sump or pan and clean it out.

Vapor Alarm

What it means: Hydrocarbon vapor was detected at the sensor.

What to check first: Check the area for a leak.

Water Out Alarm

What it means: The water table has dropped below the groundwater sensor, so it can't detect anything.

What to check first: Check the monitoring well's water level and the sensor position.

Sensor Out Alarm

What it means: The sensor is disconnected, failed or set up wrong.

What to check first: Check its wiring, then its setup.

Short Alarm

What it means: There's a short in the sensor or its wiring.

What to check first: Check the field wiring for water or damaged insulation.

Communication Alarm (also: Smart Sensor Communication Alarm)

What it means: The console can't communicate reliably with this device.

What to check first: Check its wiring, power and module.

The console itself

The console’s own printer, battery, clock, software and communication. See also: ATG console network setup.

Paper Out

What it means: The printer is out of paper.

What to check first: Load a new roll.

Printer Error

What it means: The console's printer has a problem (often the paper lever is open).

What to check first: Check the printer lever and paper.

Battery Is Off

What it means: The console's backup battery is switched off or failing, so settings are at risk if power drops.

What to check first: Turn the battery switch on or replace the battery.

Clock Incorrect

What it means: The console's clock is wrong — often a sign of a failing backup battery.

What to check first: Set the clock and check the battery.

Autodial Failed

What it means: The console couldn't send a notification or reach the network.

What to check first: Check the phone line, network and address settings.

Setup Data Warning

What it means: This device's configuration is incomplete or invalid.

What to check first: Review its setup in the console.

See these on your phone, with the explanation

TankPup watches your ATG consoles and shows every active alarm with what it means and what to check first, the same explanations as on this page. On paid plans you get a notification when an alarm starts and when it clears, so you hear about a Sudden Loss or a PLLD shutdown before a customer does.

TankPup is a convenience tool, not a safety, compliance or leak-detection system. It doesn't replace your console's own alarms, or any monitoring, testing, inspections or records you're required to keep.

Veeder-Root, Gilbarco Veeder-Root, TLS-350, TLS-450PLUS, TLS4, Franklin Fueling Systems, EVO, OPW, ProGauge and MagLink are trademarks of their respective owners. TankPup is independent and is not affiliated with, endorsed by or sponsored by them; their names are used only to say which consoles TankPup works with.

Guides: ATG alarms explained · How to check your ATG console remotely · ATG console network setup · Tank alarm notifications on your phone · How to stick a fuel tank · Water in your fuel tank · Tank chart calculator
Consoles: Veeder-Root TLS-350 · Veeder-Root TLS-450PLUS · Franklin Fueling EVO 600 / 6000 · OPW ProGauge MagLink LX · TankPup Relay · FAQ